Sodium-Ion BMS: Voltage Curves, SOC and Balancing

Home / News and Blog / Sodium-Ion BMS: Voltage Curves, SOC and Balancing
Sodium-Ion BMS: Voltage Curves, SOC and Balancing
16 Nov 2026

Two complaints account for most sodium BMS support tickets: state of charge that moves without reason, and a charge refusal in cold weather. Neither is a faulty board. Both come from settings written for lithium.

Complaint 1: “the SOC jumps from 60% to 35%”

State of charge on a sodium cell cannot be read from voltage the way it can on a lithium cell with a flat plateau. Sodium’s curve is sloped and the slope changes with temperature and age, so a voltage lookup drifts.

The fix is coulomb counting with periodic correction at the ends of the range: count charge in and out, then re-anchor at a known full or empty. The anchoring has to happen where the curve is steep, not in the middle where it is flat.

Complaint 2: “it won’t charge at −5 °C”

The BMS is doing its job. The charge cut-off temperature is a cell property, not a board preference, and below it the correct behaviour is to refuse rather than plate sodium on the anode.

What the customer needs is a warm-up path: a heater, or a charge schedule that starts when the pack has been in a warm bay. The setting is right; the system around it is missing.

The three settings worth reviewing first

Cell voltage limits — taken from the cell datasheet, not from an LFP default. Balance threshold — on a sloped curve, balancing near the top of the range is more reliable than mid-range.

Temperature derating — the current limit at low and high temperature should follow the cell’s curve, not a single number. A BMS that clamps to one value at every temperature will either overheat the pack or underuse it.

What to specify to a BMS supplier

Cell model, charge and discharge cut-offs, temperature derating curve, balancing strategy, communication protocol, and the pack topology. Five of those six are one page of data; without them the board is configured by guesswork.

Then test at the temperature extremes, not at room temperature. Most of these complaints would have been found in a freezer.

Why an SOC-OCV table is part of the specification

The 10 Ah 32140 datasheet carries a full SOC-OCV table because the voltage curve is the only state-of-charge anchor a BMS gets, and it shifts with temperature and age. On a 220 Ah prismatic cell the BMS also enforces the charge envelope: nothing at or below −10 °C, 0.20C between −30 °C and 0 °C.

Where to go next

Questions we get asked about this

Why does my sodium SOC drift more than on LFP?

The voltage curve is sloped and temperature-dependent, so voltage-based estimation drifts. Coulomb counting with end-point correction is the reliable method.

What is the charge cut-off temperature?

It is cell-specific and stated in the datasheet. Below it, charging must be refused or current-limited until the pack warms.

Can a lithium BMS be reused for sodium?

Sometimes, if thresholds, balance points and temperature derating are reprogrammable. Default LFP settings are wrong for a sodium cell.