Three-phase power calculator

Convert between kW, kVA and amps on a three-phase supply, then check the DC current the battery sees at the PCS input.

Home / Three-Phase Power Calculator

Storage cabinets are quoted in kW at the grid side and in kWh at the battery side. The bridge between them is the inverter efficiency and the DC bus voltage — both decide the cable you need between pack and PCS.

kVA = kW ÷ PF · Amps = kVA × 1000 ÷ (√3 × V)

Inputs

kW
%
V

Roughly the pack’s nominal voltage. 800 V for a commercial PCS, 51.2 V for a 16S pack.

Grid and battery side

—

 

  • Real power—
  • Apparent power—
  • Line current—
  • Per phase—
  • DC current at the PCS—
  • DC cable (3 m run, 2% drop)—
  • Energy per hour—

Figures are for a balanced three-phase load. A single-phase load on one leg draws three times the current of the balanced case, so size that leg separately. DC current assumes the inverter efficiency you entered and ignores battery round-trip losses.