Skip to content
New product 12 V 100 Ah sodium-ion truck starting battery, 1500 CCA, Group 31T See the launch →
Home / Products / Batteries / By Application / Telecom Base Stations

Telecom Base Stations

Showing all 1 results

CE, MSDS, UN38.3 and ISO certified

Rack-mount sodium-ion batteries for telecom sites

48 V · 160 Ah · 8.2 kWh · 5U

  • 19-inch rack mount A 5U case that bolts into the rack the lead-acid string came out of, with the same 48 V nominal and rectifier-compatible float voltages.
  • Built-in BMS Cell voltage, current and temperature monitored on board, with fault protection and reporting to the site controller; 4G telemetry optional.
  • −40 to +60 °C Discharges across the range an unheated shelter or a pole-mounted cabinet actually sees, with no separate thermal system.
  • Maintenance-free No watering and no equalisation charge, at a whole-life cost quoted more than 60% below the lead-acid string it replaces.
Electric two-wheeler and cargo tricycle

48 V 160 Ah 5U rack sodium-ion battery — telecom backup

48V160Ah-5U · 18S1P · regular or heated version

Cell configuration
18S1P
Chemistry
Sodium-ion (Na-ion)
Nominal voltage
51.3 V
Weight
120 ±10 kg
IP grade
IP21
Form
Rack-mount, 5U
Nominal capacity
160 Ah
Minimum capacity
≥155 Ah
Rated energy
8,200 Wh
Operating voltage range
36.0–62.1 V
Fast-charge voltage
62.1 ±0.2 V
Float charge voltage
54.0–56.7 V
Low-voltage cut-off
36.0–39.6 V
Standard charge current
80 A
Recommended charge current
≤80 A
Maximum charge current
200 A
Standard discharge current
80 A
Recommended discharge current
≤80 A
Maximum discharge current
300 A
Peak discharge current
300 A for 3 s
Internal resistance
≤20 mΩ
Charge temperature
0 to +60 °C
Discharge temperature
−40 to +60 °C
Cycle life
>3,000 cycles (25 °C, 0.5C, 30% DoD)
Dimensions
815 × 482.6 × 222 mm (5U)
Packing dimensions
860 × 550 × 290 mm
BMS
Built in — state monitoring, fault protection, communication; 4G optional
Bluetooth
Supported
Mounting
Standard 19-inch rack
Module 18S1P Battery module