Cable and busbar sizing

How thick does the cable need to be? Enter the current, the run and the drop you can live with — get the cross-section, the AWG equivalent, the loss and a fuse rating.

Home / Cable and Busbar Sizing

Two different limits decide a cable: how much current it can carry before the insulation overheats, and how much voltage it loses over the run. A short 100 A link is decided by ampacity; a long 48 V run is usually decided by volt drop.

Area (mm²) = 2 × Length (m) × Current (A) × ρ ÷ (Voltage × Drop)

Inputs

A
V
m

Cable from the pack to the load. The calculator doubles it for the return path.

%

2% is a good target; 3–5% is accepted on long low-voltage runs.

Recommended conductor

—

 

  • By ampacity—
  • By voltage drop—
  • Chosen size—
  • AWG equivalent—
  • Actual drop—
  • Loss in the cable—
  • Fuse rating—

Ampacity figures are for single-core flexible cable in free air at 30 °C ambient. Bundled cables, high ambient temperatures and long battery runs need the next size up. Fuse at 1.25× the continuous current, and check the fuse’s own interrupting rating.