UPS Rack Battery — Sodium-ion Modules for Data Rooms

Home / News and Blog / UPS Rack Battery — Sodium-ion Modules for Data Rooms
UPS Rack Battery — Sodium-ion Modules for Data Rooms
16 Nov 2026

A data-room UPS discharges for minutes, not hours, and sits at float for the rest of the year. That duty rewards a chemistry that holds charge quietly and delivers current instantly.

10–30 mintypical runtime
2C+the rate short runtime demands
48 Vcommon string voltage
RS485 / CANhow the UPS knows the state

What the rack needs

UPS class Runtime String
Server room 10–20 kVA 10–15 min 48 V, 100–200 Ah
Data hall 100 kVA 5–10 min Higher-voltage strings
Edge cabinet 5–30 min 48 V, 50–100 Ah

Short runtime means high rate. A 100 Ah pack delivering 200 A is a 2C discharge, which is ordinary for sodium and hard on a small lead-acid block.

How to size the string

1. Load. Take the real IT load, not the UPS rating. A 20 kVA UPS is often loaded to 12 kVA.

2. Runtime. kWh needed = load × hours. A 12 kW load for 15 minutes is 3 kWh.

3. Rate check. 12 kW from a 48 V string is 250 A. Confirm the pack’s continuous rating at the aisle temperature, and that the inverter’s DC input can accept the string’s voltage window.

Temperature in the room

Server rooms run at 22–27 °C, which is kind to any chemistry. The problem is usually the battery room, not the data hall. Sodium’s advantage is that a cold room needs no heating and a warm room needs no active cooling at moderate rate.

What to specify

Runtime at the actual load, ambient range, communication to the UPS (dry contact, RS485 or CAN), and the reporting the facilities team needs. Without the communication, the UPS cannot know the pack’s state and will treat it as a dumb string.

Where it is the wrong choice

An existing compliant VRLA string. Replacing it early buys nothing.

A legacy UPS with a fixed voltage window. If it cannot be told the pack’s limits, a different chemistry adds risk.

Questions buyers ask

Can the UPS charge it directly?

If the float and recharge voltages sit inside the pack’s window, yes. Otherwise the UPS needs a different profile.

Will it need more cooling?

At short runtime, self-heating is small. The bigger factor is the room temperature the string sits in.

How do we test runtime?

With a controlled discharge at commissioning and annually. Ask for the state-of-health trend, not just a pass or fail.

Is it a drop-in for a 48 V string?

Electrically yes, with the right settings and communication. The rack, terminals and fuse must match.

Where to go next

Products for this application

ESS 4 models · specs and sizes 25 kW / 40.9 kWh high-voltage C&I ESS cabinet single product · full specification

Have a specification question this article does not answer? Send it with the numbers you already have.

Request a quote

Part of

More guides in this group